MCZ OVP SL prenaponska zaštita
- zaštita instrumenata,
- 24VUC,
- 1,25A
-
Discharge current, Iimp (10/350 µs) 1 kA Discharge current, max. (8/20 µs) 5 kA Fuse 1.3 A Inductance L and L1 35 µH Lightning test current Iimp (10/350 µs) 1 kA Limiting frequency (-3 dB) at load resistance 500 kHz 240 Ω Load resistance (for limiting frequency) 240 Ω Max. continuous voltage, Uc (AC) 28 V Operating current, Imax. 1.25 A Operating voltage 34 V Protection level on output side Wire-PE 1kV/µs, typically 40 V Protection level on output side Wire-PE 8/20 µs, typically 65 V Protection level on output side Wire-wire 1 kV/µs, typically 80 V Protection level on output side Wire-wire 8/20 µs, typically 130 V Rated current IN 1.25 A Rated voltage (AC) 24 V Rated voltage (DC) 24 V Rated voltage (DC), max. 38 V Requirements category acc. to IEC 61643-21 D1 Response time ≤ 100 ps Voltage type AC/DC Volume resistance 1.00 Ω